Step | Action | Yes | No | ||||
---|---|---|---|---|---|---|---|
1 | Were you sent here from the A/C System Performance Test? | ||||||
2 |
Are the cooling fans ON and operating properly? | ||||||
3 | Visually inspect for restricted air flow at the condenser.
Is the air flow through the condenser restricted | ||||||
4 |
Is the repair complete? | -- | |||||
5 | Repair the cooling fan operation fault. Refer to Cooling Fan Inoperative in Engine Cooling. Is the repair complete? | -- | |||||
6 |
Caution: Refer to Moving Parts and Hot Surfaces Caution in the Preface section. Feel the liquid line on both sides of the expansion device. Is the temperature the same before and after the expansion device? | ||||||
7 |
Is the repair complete? | -- | |||||
8 | Air is in the refrigerant system, or the system is overcharged. Refer to the view screen on the J 43600 for air or foreign gas content in the refrigerant. Recover and recharge the A/C system. Refer to Refrigerant Recovery and Recharging . Is the repair complete? | -- | |||||
9 | Take readings of the low and high side pressures as well as the IP outlet air temperature after repairs are performed. Compare the pressures and outlet temperature to those listed in the A/C Performance Chart. Refer to Air Conditioning (A/C) System Performance Test . Are the readings within the specified ranges ? | ||||||
10 | Operate the system in order to verify the repair. Did you correct the condition ? | System OK | Go to Symptoms - HVAC Systems - Manual or Symptoms - HVAC Systems - Automatic |