Step  | Action  | Yes  | No  | ||||||
|---|---|---|---|---|---|---|---|---|---|
DEFINITION: The low and the high side pressures are both higher than normal. 
 
 
  | |||||||||
1  | Were you sent here from the A/C System Performance Test?  | Go to Step 2  | |||||||
2  | 
 Are the cooling fans ON and operating properly?  | Go to Step 3  | Go to Step 5  | ||||||
3  | Visually inspect for the following conditions: 
 
 
 Do any of these conditions exist?  | Go to Step 4  | Go to Step 6  | ||||||
4  | Repair the air flow restriction. Is the repair complete?  | Go to Step 7  | --  | ||||||
5  | Repair the fault to the cooling fan operation. Refer to Cooling Fan Inoperative . Is the repair complete?  | Go to Step 7  | --  | ||||||
6  | Air is in the refrigerant system, or the system is overcharged. Refer to the view screen on J 43600 ACR 2000 Air Conditioning Service Center for foreign gas content in the refrigerant. Recover and recharge the A/C system. Refer to Refrigerant Recovery and Recharging . Is the repair complete?  | Go to Step 7  | --  | ||||||
7  | 
 Are the readings within the specified ranges listed in the A/C Performance table?  | Go to Step 8  | |||||||
8  | Operate the system in order to verify the repair. Did you find and correct the condition?  | System OK  | |||||||