Step  | Action  | Value  | Yes  | No  | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
DEFINITION: The high and low side pressures may be normal or slightly less than normal. 
 
 
  | ||||||||||
1  | Were you sent here from the A/C System Performance Test?  | --  | Go to Step 2  | |||||||
2  | Refer to the panel air outlet temperatures recorded during the A/C system performance test. Does the discharge air temperature between the right and left center panel outlets vary by more than 1-2°C (2-3°F)?  | --  | Go to Step 7  | Go to Step 3  | ||||||
3  | Did the customer mention that the A/C system output temperatures are good at first, but then turn warm during extended drives?  | --  | Go to Step 4  | Go to Step 5  | ||||||
4  | Increase engine speed to 2000 RPM. During extended operation of the A/C system, does the low side pressure decrease, possibly accompanied by heavy frost on the liquid line between the expansion device and the evaporator?  | --  | Go to Step 5  | |||||||
5  | 
 Caution: Refer to Moving Parts and Hot Surfaces Caution in the Preface section. 
 
 
 Do the listed conditions exist?  | --  | Go to Step 7  | Go to Step 6  | ||||||
6  | 
 
 
 
 Do the listed conditions exist?  | --  | Go to Step 8  | Go to Air Temperature Malfunction for manual systems OR Air Temperature Malfunction for automatic systems  | ||||||
7  | The A/C system may be undercharged. 
 Is the action complete?  | --  | Go to Step 14  | --  | ||||||
8  | The A/C system may be contaminated. View the information screen on J 43600 ACR 2000 Air Conditioning Service Center for detection of foreign gases in the A/C system. Do foreign gases exist?  | --  | Go to Step 9  | Go to Step 10  | ||||||
9  | 
 Is the action complete?  | --  | Go to Step 14  | --  | ||||||
10  | The A/C system may contain too much moisture or air. 
 Are the panel outlet temperatures within the specified ranges of the A/C Performance Test Table?  | --  | Go to Step 15  | Go to Step 11  | ||||||
11  | The A/C system may contain too much refrigerant oil. 
 Was more than the specified amount of refrigerant oil drained from the accumulator?  | 148 ml (5 oz)  | Go to Step 12  | Go to Step 13  | ||||||
12  | 
 Are the actions complete?  | --  | Go to Step 14  | --  | ||||||
13  | 
 Are the actions complete?  | --  | Go to Step 14  | --  | ||||||
14  | 
 Are the high and low side pressures and I/P panel outlet temperatures within specifications?  | --  | Go to Step 15  | |||||||
15  | Operate the system in order to verify the repair. Did you find and correct the condition?  | --  | System OK  | Go to Symptoms - HVAC Systems - Manual OR  | ||||||