| Table 1: | Gray Area Diagnosis and Service | 
| Table 2: | Striped Area Diagnosis and Service | 
The compressor is a scroll compressor that matches the air conditioning demand by changing the compressor stroke, instead of cycling the compressor clutch. A capacity control valve located in the compressor senses the low side pressure and causes the compressor to adjust to A/C cooling demands. The compressor always runs and the system does not cycle. However, the compressor may cycle if the cooling load is not reduced enough by the capacity control valve.
| • | Check the proper operation of the cooling fans. | 
| • | Check for system voltage above 10.5 Volts. | 
| • | Check the A/C fuse and replace as necessary. | 
| • | Check the A/C blower operation and repair as necessary. | 
| • | Check the clutch coil electrical connection and repair as necessary. | 
| • | Check the drive belt and replace if damaged or missing. | 
| • | Check the condenser for restricted air flow and clean as necessary. | 
Refer to the following tables when you are diagnosing insufficient cooling complaints.
Step  | Action  | Value(s)  | Yes  | No  | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
1  | Inspect for any stored DTCs. Are any DTCs stored?  | --  | Go to Step 3  | Go to Step 2  | ||||||
2  | Connect the J 39500-B . Are the pressures above 350 kPa (50 psi)?  | --  | Go to Step 4  | Go to Step 8  | ||||||
3  | Correct any stored DTCs. Refer to Diagnostic Trouble Code (DTC) List . Does the complaint persist?  | --  | Go to Step 1  | System OK  | ||||||
4  | Inspect and correct for a blown Air Conditioner (A/C) fuse. Does the complaint persist?  | --  | Go to Step 5  | System OK  | ||||||
5  | 
 Does the A/C clutch rotate smoothly?  | --  | Go to Step 6  | System OK  | ||||||
6  | Inspect and correct for the following conditions: 
 
 
 Does the complaint persist?  | --  | Go to Step 7  | |||||||
7  | Read the DCS for Bulletins and Hints. Follow the procedures indicated. Does the complaint persist?  | --  | Go to Step 10  | System OK  | ||||||
8  | 
 Did you find a leak?  | --  | Go to Step 9  | Go to Step 10  | ||||||
9  | 
 Does the complaint persist?  | --  | Go to Step 2  | System OK  | ||||||
10  | Perform an A/C Performance Check using the following steps: 
 Does the A/C performance meet the requirement on the Performance Chart?  | --  | Go to Step 11  | Go to HVAC High Side vs. Low Side Pressure Table  | ||||||
11  | Was the customer complaint made due to high temperature and/or high humidity?  | --  | System OK  | Go to Step 12  | ||||||
12  | Perform a leak test. Refer to Leak Testing . Did you find a leak?  | --  | Go to Step 13  | System OK  | ||||||
13  | Evacuate and recharge the A/C system. Refer to Refrigerant Recovery and Recharging . Does the complaint persist?  | --  | Go to Step 10  | System OK  | 
Problem  | Action  | ||||||||
|---|---|---|---|---|---|---|---|---|---|
| 
 Important: The clutch may cycle if the discharge pressure exceeds 2758 kPa (400 psi). or if system voltage drops below 10.5 Volts.  | |||||||||
Improper condenser operation  | Improper condenser operation may result from one of the following causes: 
 
 
 
  | ||||||||
High side refrigerant restriction  | 
  | ||||||||
Refrigerant system overcharged (high discharge and high suction pressures)  | The clutch may cycle ON/OFF and cause compressor noise. Evacuate and recharge the system with the proper amount of refrigerant. Refer to Refrigerant Recovery and Recharging .  | ||||||||
Expansion tube (orifice) blocked  | 
  | ||||||||
Air in system (High discharge and high suction pressures).  | 
  | ||||||||
Problem  | Action  | ||||||
|---|---|---|---|---|---|---|---|
The compressor is damaged internally.  | 
 
 
  | ||||||
The expansion tube (orifice) is missing.  | Feel the liquid line after the expansion tube. If the line is warm, discharge the system and inspect for proper installation of the expansion tube. If the expansion tube or O-ring is missing, replace the expansion tube. Refer to Auxiliary Expansion (Orifice) Tube Replacement .  | ||||||
The refrigerant system is undercharged.  | 
  | ||||||
The expansion tube (orifice) is blocked.  | 
  |