Temperature Valve Actuator Replacement - Right Side Dual Zone
                    
Removal Procedure
- Remove the instrument panel (I/P) compartment.
Refer to 
Instrument Panel Compartment Assembly, Door, Striker, and Latch Replacement 
 in Instrument Panel, Gages, and Console.
 
- Locate the air temperature actuator (1).
 
- Disconnect the right side air temperature actuator electrical connector (2).
 
- Remove the right side air temperature actuator
bolts/screws (1).
 
- Remove the right side air temperature actuator (2).
 
- Remove the right side air temperature actuator levers (3, 4),
if necessary.
 
Installation Procedure
Important: The actuator lever (2) can only be
inserted into the door one way.
- Install the right side air temperature actuator levers, if necessary.
 
- Check and correct the engagement between the actuator levers (1, 2).
 
| 2.1.  | Install the actuator lever (2). | 
 
| 2.2.  | Align the primary tooth (4) of the actuator lever (1) with the
gap (3) in the actuator lever (2). | 
 
- Install the right side air temperature actuator (2).
 
Notice: Refer to Fastener Notice in the Preface section.
- Install the right side air temperature actuator bolts/screws.
 
Tighten
Tighten the bolts/screws to 1.2 N·m
(11 lb in).
- Connect the right side air temperature actuator
electrical connector (2).
 
- Ensure that the clip (1) on the connector
is fully inserted to the holder on the case.
 
- Install the I/P compartment. Refer to 
Instrument Panel Compartment Assembly, Door, Striker, and Latch Replacement 
 in Instrument
Panel, Gages, and Console.
 
- Re-calibrate the actuators. Refer to 
Actuator Recalibration 
.