Step  | Action  | Value(s)  | Yes  | No  | 
|---|---|---|---|---|
1  | Did you review the HVAC system operation and perform the necessary inspections?  | --  | Go to Step 2  | Go to Symptoms  | 
2  | Verify that the blower motor Med-1 speed is inoperative. Does the blower motor operate normally?  | --  | Go to Testing for Intermittent Conditions and Poor Connections in Wiring Systems  | Go to Step 3  | 
3  | 
 Does the test lamp light?  | --  | Go to Step 5  | Go to Step 4  | 
4  | Replace the blower motor resistor. Refer to Blower Motor Resistor Replacement . Is the replacement complete?  | --  | Go to Step 8  | --  | 
5  | Connect a test lamp between CKT 63 (TAN) cavity at the heater and A/C controller connector C4 and ground. Does the test lamp light?  | --  | Go to Step 6  | Go to Step 7  | 
6  | Repair the open in CKT 63 (TAN). Is the repair complete?  | --  | Go to Step 8  | --  | 
7  | Replace the heater and A/C controller. Refer to Control Assembly Replacement . Is the replacement complete?  | --  | Go to Step 8  | --  | 
8  | Operate the system in order to verify the repair. Did you correct the condition?  | --  | System OK  | Go to Step 3  |