| Table 1: | Discharge High Pressure Abnormally High | 
| Table 2: | Discharge Pressure Abnormally Low | 
| Table 3: | Suction Low Pressure Abnormally Low | 
| Table 4: | Suction Pressure Abnormally High | 
| Table 5: | Suction and Discharge Pressure Abnormally High Charge | 
| Table 6: | Suction and Discharge Pressure Abnormally Low | 
| Table 7: | Refrigerant Leaks | 
Important: The following steps must be completed before using the symptom tables.
| • | There are no DTCs set. | 
| • | The control module(s) can communicate via the serial data link. | 
| • | Wet carpet or mats | 
| • | High humidity | 
| • | Interior water leak | 
| • | Blocked A/C evaporator drain tube | 
| • | Maximum passenger capacity | 
| • | Blocked body pressure relief valves | 
| • | Obstructed or dirty passenger compartment air filter, if equipped | 
| • | Blocked or damaged air inlet or outlet vents | 
Faulty electrical connections or wiring may be the cause of intermittent conditions. Refer to Testing for Intermittent Conditions and Poor Connections .
Refer to a symptom diagnostic procedure from the following list in order to diagnose the symptom:
Symptoms  | Checks  | Actions  | |||
|---|---|---|---|---|---|
After stopping the compressor, the pressure drops about 299 kPa (43 psi) quickly, then falls gradually.  | Air is in the system.  | Recover, evacuate, and recharge the system with the specified amount of refrigerant.  | |||
The condenser is excessively hot.  | Excessive refrigerant is in the system.  | Recover, evacuate, and recharge the system with the specified amount of refrigerant.  | |||
Reduced flow or no air flow through the condenser  | The condenser or the radiator fins are clogged.  | Clean the condenser or the radiator fins.  | |||
The condenser or the radiator fan is not working properly.  | 
 
  | ||||
The line to the condenser is excessively hot.  | A restricted flow of refrigerant is in the system.  | Locate and repair the restriction.  | 
Symptoms  | Checks  | Actions  | ||||
|---|---|---|---|---|---|---|
The condenser is not hot.  | Insufficient refrigerant is in the system.  | 
 
  | ||||
High and low pressures are balanced soon after stopping the compressor.  | A faulty compressor pressure relief valve is present.  | Repair or replace the compressor.  | ||||
Low side pressure is higher than normal.  | A faulty compressor seal is present.  | |||||
The outlet of the expansion valve is not frosted.  | A faulty expansion valve is present.  | Replace the expansion valve.  | ||||
The low pressure gage indicates vacuum.  | Moisture is in the system.  | Recover, evacuate, and recharge the system.  | 
Symptoms  | Checks  | Actions  | ||||
|---|---|---|---|---|---|---|
The condenser is not hot.  | Insufficient refrigerant is in the system.  | 
 
  | ||||
The expansion valve is not frosted and the low pressure line is not cold.  | A frozen expansion valve is present.  | Replace the expansion valve.  | ||||
The low pressure gage indicates a vacuum.  | A faulty expansion valve is present.  | |||||
The discharge temperature is low and the airflow from the vents is restricted.  | The evaporator is frozen.  | Clear the restricted evaporator case drain.  | ||||
The expansion valve is frosted.  | The expansion valve is clogged.  | Clean or replace the expansion valve.  | ||||
The receiver/dryer outlet is cool and the inlet is warm.  | The receiver/dryer is clogged.  | Replace the receiver/dryer.  | 
Symptoms  | Checks  | Actions  | 
|---|---|---|
The low-pressure hose and the check joint are cooler than the temperature around the evaporator.  | The expansion valve is opened for too long.  | Replace the expansion valve.  | 
The capillary tube is loose.  | ||
Suction pressure is lowered when the condenser is cooled by water.  | Excessive refrigerant is in the system.  | Recover, evacuate, and recharge the system.  | 
High and low pressure are equalized as soon as the compressor is stopped and both gages fluctuate while the compressor is running.  | A faulty gasket is present.  | Repair or replace the compressor.  | 
A faulty high-pressure valve is present.  | ||
Foreign particles are stuck in the high-pressure valve.  | 
Symptoms  | Checks  | Actions  | |||
|---|---|---|---|---|---|
Airflow through the condenser is reduced.  | The condenser or the radiator fins are clogged.  | Clean the condenser and the radiator.  | |||
The radiator cooling fans are not working properly.  | 
 
  | ||||
The condenser is excessively hot.  | Excessive refrigerant is in the system.  | Recover, evacuate, and recharge the system.  | 
Symptoms  | Checks  | Actions  | 
|---|---|---|
The low-pressure hose and metal end areas are cooler than the evaporator.  | The low-pressure hose is clogged or kinked.  | Repair or replace the low-pressure hose.  | 
The temperature around the expansion valve is low compared to the temperature around the receiver/dryer.  | The high pressure line is clogged.  | Repair or replace the high-pressure line.  | 
Symptoms  | Checks  | Actions  | 
|---|---|---|
The compressor clutch is dirty.  | The compressor shaft seal is leaking.  | Repair or replace the compressor.  | 
The compressor bolts are dirty.  | Leaking occurs around a compressor housing bolt.  | Tighten the bolts or replace the compressor.  | 
The compressor gasket is wet with oil.  | The compressor gasket is leaking.  | Repair or replace the compressor.  |